| Availability: | |
|---|---|
| Quantity: | |
Place of Use
◇ Compact secondary substation
◇ Small industrial and mining enterprises
◇ Wind power plant
◇ Hotel, shopping mall, office building, business center, etc
◇ C-load switch unit
◇ D-direct cable connection unit
◇ De - direct cable connection unit with earthing switch
◇ F-load switch fuse unit
◇ V-vacuum circuit breaker unit
Product classification
According to the type of switch, it can be divided into load switch with grounding assembly (referred to as C module), load switch without grounding assembly (referred to as CB module), circuit breaker with grounding assembly (referred to as V module), circuit breaker without grounding assembly (referred to as VB module), circuit breaker contact switch (referred to as VZ module), load switch+fuse combination electrical switch assembly (referred to as F module), and isolation switch assembly (referred to as G module).
- Fully Sealed
- 20-Year Maintenance-Free
- Extreme Environment Resistant
- Five-Prevention Safety
- Universal Scenario Fit
| Technical data | Scheme C | Scheme F | Scheme V | ||||||||
| Load switch | Grounding switch | Load switch fuse combination electrical appliances | Lower port grounding switch | Vacuum circuit breaker | Grounding switch /Isolation switch | ||||||
| Rated voltage | kV | 36/40.5 | 35/40.5 | 36/40.5 | 36/40.5 | 36/40.5 | 36/40.5 | ||||
| Power frequency withstand voltage | kV | 70/95 | 70/95 | 70/95 | 70/95 | 70/95 | 70/95 | ||||
| Isolation switch | kV | 80/110 | 80/110 | 80/110 | |||||||
| Lightning impulse withstand voltage | kV | 170/185 | 170/185 | 170/185 | 170/185 | 170/185 | 170/185 | ||||
| Isolation fracture | kV | 195/215 | 195/215 | 195/215 | |||||||
| Rated current | A | 630/6301' | 200/2002 | 630/630 | |||||||
| Breaking capacity | |||||||||||
| Active load | A | 630/6330 | 200/200 | ||||||||
| Closed loop current interruption | A | 630/630 | 200/200 | ||||||||
| Empty cable charging | A | 20/21 | 20/21 | 50(C1) | |||||||
| Ground fault | A | 60/63 | 60/63 | ||||||||
| Ground fault cable charging | A | 35/36 | 35/36 | ||||||||
| Transfer current | A | 840/750 | |||||||||
| Short circuit breaking current | kA | 20 (expect) | 20/20(E1, S1) | ||||||||
| Closing ability | kA | 50/50 | 50/50 | 50 (expect) | 2.5/2.5 | 50/50 | 50/50 | ||||
| Level (electrical lifespan) | E3/E2 | E2/E2 | -/- | E2/E2 | E2/E2 | E2/E2 | |||||
| Short time withstand current for 3 seconds | kA | 20/20 | 20/20 | Restricted by high-voltage fuses | 20/20 | 20/20 | |||||
| Internal arc classification | kA | 20/20 | 20/20 | 20/20 | |||||||
1. Commercial Complexes & High-Rise Residential
Modern commercial complexes and high-rise residential buildings require reliable, compact, and fire-safe power distribution equipment.
2. Industrial Parks & Heavy Manufacturing
Industrial parks and heavy manufacturing facilities, including steel mills, cement plants, chemical factories, and automotive assembly lines, consume large volumes of medium-voltage power and require robust, outdoor-rated distribution equipment.
3. PV & Energy Storage Grid Connection
Solar photovoltaic farms and battery energy storage systems (BESS) require dedicated step-up transformer solutions to interface with the medium-voltage grid.
4. Infrastructure — Rail Transit, Healthcare & Data Centers
Critical infrastructure applications, including metro and railway systems, hospitals, and data centers, demand the highest levels of power reliability and redundancy.
5. Municipal & Environmental — Water Treatment & Pumping Stations
Municipal water supply, wastewater treatment plants, and flood control pumping stations present challenging operating conditions for electrical distribution equipment.
Q:Are you a trading company or factory?
A:We are a manufacturer boasting 15 years of industry experience and holding proprietary import-export rights.
Q:What certifications do you have?
A:Yes, we hold ISO, CE, and IEC certificates. In addition, we possess a number of design patents and a Special Equipment Manufacturing License.
Q:How long is your delivery time?
A:For normal products in 7-10 days; For bulk order, in 15-25 days. It depends.
Q:What is the warranty time?
A:3 years warranty for all of our stainless steel products. Gaskets or the easy broken parts are not included due to the different application for customers.