| Availability: | |
|---|---|
| Quantity: | |
Distribution, control and protection. HBSRM-12 adopts a fully sealed structure, all of which are sealed in a gas chamber welded by a stainless steel plate with a protection rating of IP67.
It can adapt to humid and salty fog, such as flood, heavy pollution and other harsh environmental conditions, and operate safe and reliable multi-loop ring network switchgear.Widely used in industrial parks, streets, airports,
Residential areas, prosperous commercial centers, etc., are ideal equipment for distribution network automation.Also used in: compact box-type substations, cable branch boxes, opening and closing, wind power stations, subways and tunnels.
- Fully Sealed
- 20-Year Maintenance-Free
- Extreme Environment Resistant
- Five-Prevention Safety
- Universal Scenario Fit
| Serial No. | Project | C Module | F Module | V Module | |||||
| Load switch | Combination Electrical Appliances | Vacuum circuit breaker | Lsolation/Grounding Switch | ||||||
| 1 | Rated voltage (kV) | 12 | 12 | 24 | 24 | ||||
| 2 | 1min Power frequency withstand voltage (kV) | 42/48 | 65/79 | ||||||
| 3 | Lightning impulse withstand voltag (kV) | 75/85 | 125/145 | ||||||
| 4 | Rated current (A) | 630 | 125* | 630 | 630 | ||||
| 5 | Turn on and off current | ||||||||
| Closed-loop interrupting current (A) | 630 | ||||||||
| Cable Charging Opening Current (A) | 10 | ||||||||
| 5% Active Load Open-Out Current (A) | 31.5 | ||||||||
| Grounding fault interruption current (A) | 31.5 | ||||||||
| Short circuit breaking current (kA) | 31.5* | 20 | |||||||
| 6 | Short-circuit closing current (kA) | 63 | 80* | 20 | |||||
| 7 | Short-circuit withstand current (kA) | 20 | 20 | 20 | |||||
| 8 | Short circuit duration (s) | 4 | 4 | 4/2 | |||||
| 9 | Mechanical life time | 5000 | 5000 | 10000 | 10000 | ||||
| 10 | SF6 Gas Pressure (bar) | 1.2/12 1.4/24 (20°C) | |||||||
| 11 | Annual leak rate | 0.10% | |||||||
| 12 | Protection Level | IP67/4X (Gas tank/Enclosure) | |||||||
| Serial No. | Project | C Module | F Module | V Module | ||||||||||
| Load switch | Combination Electrical Appliances | Vacuum circuit breaker | Lsolation/Grounding Switch | |||||||||||
| 1 | Rated voltage (kV) | 40.5 | ||||||||||||
| 2 | 1min power frequency withstand voltage (kV) | 95/118 | ||||||||||||
| 3 | Lightning impulse withstand voltage(kV) | 185/215 | ||||||||||||
| 4 | Rated current (A) | 630 | 80* | 630 | 1250 | 630 | 1250 | |||||||
| 5 | Rated Closed-loop interrupting current(A) | 630 | ||||||||||||
| 6 | Rated Cable Charging Opening Current(A) | 21 | ||||||||||||
| 7 | 5% Active Load Open-Out Current (A) | 31.5 | ||||||||||||
| 8 | Grounding fault interruption current (A) | 63 | ||||||||||||
| 9 | RatedShort circuit breaking current (kA) | 31.5* | 20 | 25 | ||||||||||
| 10 | Rated short circuit closing current (kA) | 50 | 80* | 50 | 63 | 50 | 63 | |||||||
| 11 | Rated short circuit withstand current (kA) | 20 | 20 | 25 | 20 | 25 | ||||||||
| 12 | Rated short circuit duration (s) | 4 | 4 | 4 | ||||||||||
| 13 | Mechanical life time | 5000 | 5000 | 10000 | 5000 | |||||||||
| 14 | SF6 Gas Pressure (bar) | 1.4/ (20°C) | ||||||||||||
| 15 | SF6 Annual leak rate | 0.10% | ||||||||||||
| 16 | Protection Level | IP67/4X (Gas tank/Enclosure) | ||||||||||||
| * Indicates that depends on or is limited by a fuse. | ||||||||||||||
1. Commercial Complexes & High-Rise Residential
Modern commercial complexes and high-rise residential buildings require reliable, compact, and fire-safe power distribution equipment.
2. Industrial Parks & Heavy Manufacturing
Industrial parks and heavy manufacturing facilities, including steel mills, cement plants, chemical factories, and automotive assembly lines, consume large volumes of medium-voltage power and require robust, outdoor-rated distribution equipment.
3. PV & Energy Storage Grid Connection
Solar photovoltaic farms and battery energy storage systems (BESS) require dedicated step-up transformer solutions to interface with the medium-voltage grid.
4. Infrastructure — Rail Transit, Healthcare & Data Centers
Critical infrastructure applications, including metro and railway systems, hospitals, and data centers, demand the highest levels of power reliability and redundancy.
5. Municipal & Environmental — Water Treatment & Pumping Stations
Municipal water supply, wastewater treatment plants, and flood control pumping stations present challenging operating conditions for electrical distribution equipment.
Q:Are you a trading company or factory?
A:We are a manufacturer boasting 15 years of industry experience and holding proprietary import-export rights.
Q:What certifications do you have?
A:Yes, we hold ISO, CE, and IEC certificates. In addition, we possess a number of design patents and a Special Equipment Manufacturing License.
Q:How long is your delivery time?
A:For normal products in 7-10 days; For bulk order, in 15-25 days. It depends.
Q:What is the warranty time?
A:3 years warranty for all of our stainless steel products. Gaskets or the easy broken parts are not included due to the different application for customers.